plc automation

Hotline

Yokogawa YTA70P Temperature Transmitter Panel mount type rail mount

description: The YTA70P is a Panel mount type of temperature transmitter that accepts thermocouples, RTDs, ohms or DC millivolts input and converts it to a 4 to 20 mA DC signal for transmission....
BASIC INFO

Yokogawa YTA70P Temperature Transmitter Panel mount type DIN rail mount

 

 

 The YTA70P is a Panel mount type of temperature transmitter that accepts thermocouples, RTDs, ohms or DC millivolts input and converts it to a 4 to 20 mA DC signal for transmission. The YTA70P conforms to the standard DIN rail mounting. The YTA70P supports HART® communication protocol. HART protocol revision is HART 7, and it features long tag number up to 32 characters, enhanced burst mode and event notification, and command aggregation function. 

 

 

The YTA70P delivers the characteristics of both converters and transmitters. It has a space-saving design that offers low cost installation. The HART® 7 protocol allows you to conveniently configure the transmitter using the latest FDT/DTM technology. HART® 7 benefits include long tag, enhanced burst mode, and event notification. The YTA70P is the choice for rail-mounted control applications.

YTA70P features include:

  • 4 to 20 mA DC Analog Output
  • HART® 7 Digital Protocol Output
  • 17 input types
  • Rail-mount

 
STANDARD SPECIFICATIONS


Cold Junction Compensation Accuracy
(For T/Cs only)
±1°C (±1.8°F)
Power Supply Effects
±0.005% of FS per Volt
EMC Conformity
CE: EN61326-1, EN61326-2-3, EN 55011
KC: Korea Electromagnetic Conformity standard.
Class A
RCM: EN61326-1, EN 55011
EU RoHS Directive
Applicable standard: EN 50581
Input Type, Span and Range
Selection from thermocouples (T/Cs), 2-, 3-, and 4-
wire RTDs, ohms and DC millivolts.
See Table 1.
Maximum Zero offset
±50% of selected maximum value
Input Resistance (for thermocouples, mV)
10 MΩ, or 3 kΩ at power-off
Input Lead Wire Resistance (for RTDs, ohms)
5 Ω per wire or lower
(up to 50 Ω per wire is configurable with reduced
measurement accuracy)
Sensor Burnout
High (NAMUR NE43 upscale) , Low (NAMUR NE43
downscale) or value within 3.5 to 23 mA
Output
Two wire 4 to 20 mA DC
Response Time
1 to 60 seconds programmable
Ambient Temperature Limits
(Option code may affects limit)
-40 to 60°C (-40 to 140°F)
Ambient humidity limits
0% to 95% RH (non-condensation)
Isolation
Input/output isolated to 1500 V AC

Supply & Load Requirements:
Voltage
8 to 35 V DC for operation
(8 to 30 V DC for Intrinsically safe type)
13.8 to 35 V DC for digital communication
Load Resistance
0 to (E-8)/0.0236 [Ω]
where E is power supply voltage.
250 to 600 Ω for digital communication

 

Yokogawa YTA70P Temperature Transmitter Panel mount type DIN rail mount

-----------------------------------